# Equipment data dictionary loaded by secs_server at startup. Adding a # capability (SVID, ECID, CEID, alarm, recipe, command) is a YAML edit; # no code change is required as long as the underlying message handler # already exists in the C++ Router. device: id: 0 model_name: "SECSGEM-SIM" software_rev: "0.1.0" equipment_type: "EQUIPMENT" # S1F20 EQPTYP string # Reported on S1F19 -> S1F20 (Get GEM Compliance). CCODE values follow # E30 Appendix A; CDESC is implementer-defined. Keep this list honest: # it should reflect what the equipment actually implements (see # COMPLIANCE.md for the audit). capabilities: - {code: 1, name: "Establish Communications"} - {code: 2, name: "Dynamic Event Report Configuration"} - {code: 3, name: "Variable Data Collection"} - {code: 5, name: "Status Data Collection"} - {code: 6, name: "Alarm Management"} - {code: 7, name: "Remote Control"} - {code: 8, name: "Equipment Constants"} - {code: 9, name: "Process Program Management"} - {code: 11, name: "Equipment Terminal Services"} - {code: 12, name: "Clock"} - {code: 14, name: "Spooling (partial; S2F43/F44 + S6F23/F24)"} - {code: 15, name: "Control (operator initiated)"} # GEM300 extensions (declared so the host can probe with S1F19). - {code: 40, name: "E40 Process Job Management"} - {code: 94, name: "E94 Control Job Management"} # Reported on S1F3 (values) and S1F11 (namelist). `value` is the initial. # `type` controls the SECS-II Item format. svids: - {id: 1, name: ControlState, units: "", type: ASCII, value: ""} - {id: 2, name: Clock, units: "", type: ASCII, value: ""} - {id: 3, name: EventsEnabled, units: "", type: BOOLEAN, value: true} # Reported on S1F21/F22 (DVID namelist). Same shape as SVIDs. dvids: - {id: 100, name: WaferCounter, units: "wafer", type: U4, value: 0} - {id: 101, name: ChamberPressure, units: "Torr", type: F4, value: 0.000001} # Reported on S2F13 (values) / S2F29 (namelist) / S2F15 (set). ecids: - {id: 10, name: TimeFormat, units: "code", type: U4, value: 1, min: "0", max: "1"} - {id: 11, name: EstablishCommTimeout, units: "sec", type: U4, value: 10, min: "1", max: "60"} # Reported on S6F11. The host links these to reports via S2F35 and # enables them via S2F37. ceids: - {id: 100, name: ControlStateChanged} - {id: 200, name: AlarmSetEvent} - {id: 300, name: ProcessStarted} - {id: 400, name: ControlJobExecuting} # E94 CJ entered Executing - {id: 401, name: ControlJobCompleted} # E94 CJ entered Completed # Reported on S5F5 / S5F1. `category` is the lower-7 of ALCD. alarms: - {id: 1, text: "Chiller Temp High", category: 4} - {id: 2, text: "Door Open", category: 1} # Reported on S7F19. Body served by S7F5/F6. recipes: - {id: "RECIPE-A", body: "STEP CHAMBER ARGON 30s\nSTEP CHAMBER NITROGEN 60s\nEND"} - {id: "RECIPE-B", body: "STEP HEATER 800C 120s\nEND"} # Dispatched by S2F41. `ack` is the HCACK enum value. Optional `emit_ceid` # fires a CEID after dispatch (e.g. ProcessStarted on START), and optional # `set_alarm` activates an alarm (e.g. FAULT -> alarm 1). `force_spool` # (true/false) flips the spool store's test-force flag — for the demo this # stands in for "the host link has gone down" without actually dropping # TCP. host_commands: - {name: START, ack: Accept, emit_ceid: 300} - {name: STOP, ack: Accept} - {name: PAUSE, ack: CannotDoNow} - {name: FAULT, ack: Accept, set_alarm: 1} - {name: SPOOL_ON, ack: Accept, force_spool: true} - {name: SPOOL_OFF, ack: Accept, force_spool: false} # Spool (E30 §6.22). Streams listed here may be queued by the equipment # when the host is unreachable; queued messages drain when the host sends # S6F23 with RSDC=0. max_size caps the in-memory queue (FIFO eviction on # overflow). spool: max_size: 100 spoolable_streams: [5, 6] # CEID emitted automatically whenever the control state machine transitions # (i.e. on every change-handler call). Set to null to disable. emit_on_control_change: 100